Solid State Equipment NZ

Automatic earthquake gas isolation. NZ-made since 1971.

AS 1170.4 Section 8 — Seismic Design for Building Services and Gas

Last reviewed: October 2026

AS 1170.4 is Australia's earthquake actions standard. Most people know it as a structural standard, but Section 8 applies to everything attached to the structure: ceilings, partitions, and the building services that run through it. That includes gas pipework, boilers and plant. This page explains what AS 1170.4 Section 8 asks of building services, what changed in the 2024 edition, and what it doesn't cover.

Where AS 1170.4 sits in the NCC

The National Construction Code (NCC) requires Class 2 to 9 buildings to perform adequately under earthquake actions. AS 1170.4 is the Deemed-to-Satisfy route to meeting that requirement. NCC 2025 references the 2024 edition, AS 1170.4:2024, which supersedes the 2007 edition. NCC 2022 referenced the 2007 edition. Which one applies to a project depends on the NCC edition in force when it was approved, and states adopt NCC editions on their own timelines.

Section 8 is not optional detail. In 2019, state regulators and the Australian Building Codes Board reminded industry of their Section 8 obligations, and Queensland's building regulator (QBCC) ran site audits focused on Section 8 compliance.

What AS 1170.4 Section 8 covers

Section 8 requires non-structural parts and components, and their fixings, to be designed for horizontal and vertical earthquake forces. The list of covered components includes:

  • boilers, water heaters and other equipment using combustible energy sources, with their flues and pressure vessels
  • fire suppression systems, including sprinkler piping
  • emergency electrical and life safety systems
  • generators and other rotating equipment
  • utility and service interfaces
  • piping, ductwork and cable trays

Design forces depend on the building's Importance Level, the site hazard factor (Z), soil class, the component's height in the building and how it is mounted. Components critical to containing hazardous materials, or needed to function straight after an earthquake, take a higher importance factor. So does every component in an Importance Level 4 building, such as a hospital. Section 8 allows some exemptions for mechanical, hydraulic and electrical components, but they don't apply in Importance Level 4 buildings, or to components that must keep working immediately after an earthquake.

What changed in AS 1170.4:2024

For building services designers, the main changes are:

  • One section for parts and components. Provisions previously spread across Sections 5 and 6 are now in Section 8.
  • Design storey drift is defined. Services in vertical risers, such as pipes, ducts and cable trays, must accommodate the movement between floors.
  • Importance Level 4 buildings must stay operational, not just serviceable, after a design earthquake. Services that must keep working need specific design, and sometimes testing.
  • Clearances between parts and components. A new informative appendix (Appendix C) gives displacement clearances so restrained and unrestrained services don't collide during shaking.

What Section 8 doesn't do: restraint is not isolation

AS 1170.4 Section 8 is about keeping components in place. Gas pipework that meets it is braced so it doesn't swing, fall or tear free. But restrained pipework can still leak. A joint can fail, a fitting can crack, or an appliance connection can break where the building moves differently from the plant. Section 8 doesn't call for automatic gas isolation, so gas keeps flowing until someone shuts it off by hand.

Automatic seismic isolation closes that gap. The Solid State Seismic Shutoff — MK6 is an electronic trigger that detects earthquake ground motion and fires a relay within 10 milliseconds. The relay closes the connected gas solenoid valve: the MK6 is the detector and trigger, not the valve itself. It has five field-adjustable sensitivity settings, from 0.012g to 0.200g, to suit the site. It doesn't replace Section 8 restraint. It works alongside it. The MK6 has been made in New Zealand since 1971. Confirm the requirements for your project with the design engineer and your state gas regulator, including approval of the gas valve it drives.

For the wider Australian picture, see earthquake gas shutoff in Australia. For what to include in a specification (detection, power, outputs and mounting), see our guide to specifying a seismic shutoff system, or download the MK6 datasheet and manual (PDF). The New Zealand counterpart to Section 8 is NZS 4219.